电网电压瞬间跌落时,S120 BLM/SLM/ALM报F06200的对应方案  

2015-11-25 10:25:39|  分类: S120 |  标签: |举报 |字号 订阅

  下载LOFTER 我的照片书  |

关于SINAMICS S120的各种电源模块对进线电压瞬间跌落的承受能力,在SINAMICS工程师手册中有详细的描述。感兴趣的朋友可以看一眼。

Engineering Manual SINAMICS G130, G150, S120 Chassis, S120 Cabinet Modules, S150 Power unit with Control Interface Module CIM and Control Unit CU320-2 with firmware ≥ 4.3)

https://support.industry.siemens.com/cs/ww/en/view/83180185

第52页,1.2.8     Supply voltage variations and supply voltage dips

--------------------------

如果电网电压有瞬间跌落,超过了LM的承受能力,那么LM会报错F06200.当然一相熔断器烧了,或进线接触器一样触点接触不良,也可能造成F06200.我这里只讲由电网电压瞬间跌落导致的F06200.

F06200 Infeed: One or several line phases failed
Drive object: A_INF, R_INF, S_INF
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Failure overvoltage in one or several line supply phases.
The fault can be output in two operating states:
1. During the power-on phase of the infeed unit.
The measured line supply angle deviates from the regular characteristic for a 3-phase system - the PLL cannot be
synchronized.
The fault occurs immediately after power-up if, when operating with a Voltage Sensing Module (VSM), the phase
assignment L1, L2, L3 at the VSM differs from the phase assignment at the power unit.
2. While the infeed is operational.
After a voltage dip has been detected or an overvoltage (note A06205) in one or several line phases a fault occurred
within 100 ms (also refer to other relevant messages). Generally, before fault message F06200 is output, Alarm
A06205 occurs at least once, whose warning value can provide information regarding the cause of the line supply
fault.
Possible causes:
- voltage dip on the line side or phase failure or overvoltage lasting longer than 10 ms.
- overload condition on the load side with peak current.
- line reactor missing.
Remedy: - check the line supply and fuses.
- check the connection and size (rating) of the line reactor.
- check and correct the phase assignment at the VSM (X521 or X522) and at the power unit.
- check the load.
- if failed in operation, carefully note the previous alarm messages A6205 with alarm values.
See also: p3463 (Infeed line angle change phase failure detection)

-----------------------

BLM、SLM、ALM也有自动再启动功能,可以在参数P1210里激活。如果现场电网真有瞬间跌落的情况,那么可以尝试P1210=4,以观后效。

Re p1210 = 4:
An automatic restart is only executed if fault F06200 has occurred. If additional faults are present, then these faults are also acknowledged and when successful, starting continues. If the 24 V Control Unit power supply fails, then this is interpreted as a line supply failure.

  评论这张
 